Operation:
The manual call points provide a textured finger-hold area that includes Braille text. In addition to PUSH IN and PULL DOWN text, there are arrows indicating how to operate the station, provided for non-English-speaking people.
Pushing in and then pulling down on the handle activates the normally-open alarm switch. Once latched in the down position , the word" ACTIVATED" appears at the top in bright yellow, with a portion of the handle protruding at the bottom as a visible flag.
Resetting the station is simple: insert the key, twist one quarter-turn, then open the station`s front cover, causing the spring-loaded operation handle to return to its original position. The alarm switch can then be reset to its normal(non-alarm) position manually(by hand) or by closing the station`s front cover, which automatically resets the switch.
Loop design and wiring:
The fire alarm control panel Zone wire can be connected to terminal loop(+), loop(-) unpolarized wire.
If the manual call point is in the end of the zone wire, a 5.6K resistance should be connected to terminal loop(+),loop(-).
Installation:
Note: All wiring must conform to applicable local codes, ordinances, and regulations.
Mounting indoor wall
Attach mounting base to wall at 1.5 meter`s(59in) high
Connect field wiring to terminals
To attach product to mounting base
Secure product by tightening the one mounting screws in the front of the product housing.
Specifications:
Non UL Listed
Operating voltage range: 9-28VDC Volts
Alarm resistance: 470ohm/1W
Operating humidity range: 10% to 93% relative humidity, non-condensing
Operating temperature range: -10¡É~50¡É (14¢µ~122¢µ)
Dimensions (LxWxH): 140x104x45mm / 5.51"x4.09"x1.77"
Net Weight: 220g / 0.44lb